ORIGINAL ARTICLE
Causes of Defects and Damage to Brick Masonry Elements in Historic Buildings
 
More details
Hide details
1
Faculty of Civil and Environmental Engineering, Department of Engineering Structures, Politechnika Gdańska, Poland
 
2
Implementation Doctoral School, Gdansk University of Technology
 
 
Submission date: 2024-09-22
 
 
Acceptance date: 2024-10-18
 
 
Online publication date: 2024-11-29
 
 
Publication date: 2024-11-29
 
 
Corresponding author
Maciej Niedostatkiewicz   

Faculty of Civil and Environmental Engineering, Department of Engineering Structures, Politechnika Gdańska, Poland
 
 
Civil and Environmental Engineering Reports 2024;34(4):423-448
 
KEYWORDS
TOPICS
ABSTRACT
Ceramic brick masonry elements constitute the largest number of structural systems of historic buildings, especially sacral and public utility buildings. In the past, they were also very commonly used as a material for the construction of military facilities. Historic buildings and masonry structures undergo destructive processes over time, the course of which can be very diverse and depends, among other things, on the physicochemical properties of the materials, the type of structure, the age of the building, working conditions and random conditions and events. The paper is an engineering review of the causes of damage to masonry structures and indicates the need for cooperation between representatives of various specialties of science and technology, in particular architectural historians, specialists in the field of conservation of monuments, structural engineers and specialists in the field of geotechnics, geology, hydrogeologists and meliorators in order to ensure the protection of masonry structures in historic buildings.
REFERENCES (28)
1.
Białkiewicz, A 2022. Zagrożenia obiektów sakralnych [Threats to sacred buildings]. XXX Konferencja Naukowo-Techniczna Awarie Budowlane-2022, 21-32, Szczecin-Międzyzdroje (in Polish).
 
2.
Błaszczyński, T, Oleksiejuk, H, Firlej, E and Błaszczyński, M 2011. Wielostopniowy monitoring i zabezpieczenie budynków pod ochroną konserwatorską przed awarią lub katastrofą [Multi-level monitoring and protection of buildings under conservator's protection against failure or disaster]. XXV Konferencja Naukowo-Techniczna Awarie Budowlane-2011, 395-402, Szczecin-Międzyzdroje (in Polish).
 
3.
Drobiec, Ł 2022. Przyczyny awarii i katastrof obiektów zabytkowych [Causes of failures and disasters of historic buildings]. XXX Konferencja Naukowo-Techniczna Awarie Budowlane-2022, 33-52, Szczecin-Międzyzdroje (in Polish).
 
4.
Gajownik, R, Jarmontowicz, R and Sieczkowski, J 2007. Diagnostyka i metody oceny bezpieczeństwa konstrukcji murowych [Diagnostics and methods of assessing the safety of masonry structures]. XXII Ogólnopolska Konferencja Warsztat Pracy Projektant Konstrukcji WPPK-2007, 647-694, Szczyrk (in Polish).
 
5.
Geryło, R and Nowogońska, B 2024. Wymogi zrównoważonego rozwoju a renowacja obiektów zabytkowych [Sustainable development requirements and renovation of historic buildings]. Przegląd Budowlany, 1-2, 24-27 (in Polish).
 
6.
Szmygin, B, Trochowicz, M, Klimek, B and Szostak, B 2018. Badania techniczne historycznych ruin [Technical research of historical ruins]. Lublin: Wydawnictwo Politechniki Lubelskiej (in Polish).
 
7.
Niedostatkiewicz, M 2021. Błędy realizacji prac remontowych przyczyna uszkodzeń wilgotnościowych zabytkowego budynku Sali BHP w Gdańsku [Errors in the implementation of renovation works caused moisture damage to the historic building of the BHP Hall in Gdańsk]. Builder, 9, 290, 50-53 (in Polish).
 
8.
Niedostatkiewicz, M 2023. Prace remontowo-naprawcze w obiektach zabytkowych. Wybrane przykłady [Renovation and repair works in historic buildings. Selected examples]. Pelplin: Wydawnictwo Bernardinum (in Polish).
 
9.
Walczak, BM 2022. Trudna rewitalizacja zabytków poprzemysłowych w Polsce – osiągnięcia i porażki [The difficult revitalization of post-industrial monuments in Poland – achievements and failures]. Ochrona Zabytków, 1, 7–28 (in Polish).
 
10.
Majewski, T, Popielski, P, Niedostatkiewicz, M and Mieszkowski, R 2023. Diagnostyka podłoża gruntowego i fundamentów zabytkowego kościoła w stanie awarii [Diagnostics of the soil and foundations of a historic church in a state of failure]. XXXVI Ogólnopolska Konferencja Warsztaty Pracy Projektanta Konstrukcji WPPK-2023, 363-423, Szczyrk (in Polish).
 
11.
Przewłócki, J, Dardzińska, I and Świniański, J 2005. Review of historical buildings’ foundations. Géotechnique, 55, 5, 363-727.
 
12.
Przewłócki, J and Zielinska, M 2016. Analysis of the Behavior of Foundations of Historical Buildings. Procedia Engineering, 161, 362-367.
 
13.
Wandzik, G, Szojda, L and Ajdukiewicz, A 2007. Zabezpieczenie budynków w obszarach ujawniania się nieciągłości deformacji terenu [Securing buildings in areas where terrain deformation discontinuities are revealed]. XXIII Konferencja Naukowo-Techniczna Awarie Budowlane-2007, 341-348, Szczecin -Międzyzdroje (in Polish).
 
14.
Topolnicki, M 2004. Podchwycenie i wzmocnienie fundamentów kościoła św. Jana w Gdańsku metodą iniekcji strumieniowej [Lifting and strengthening the foundations of St. John's Church in Gdańsk using the jet injection method]. Międzynarodowe Seminarium CURE „Rewitalizacja budowli miejskich”, Gdańsk, 83-92 (in Polish).
 
15.
Rouba, BJ, 2017-2019. Zawilgocenie-problem opiekuna Kościoła. Materiał niepublikowany, przekazany Radzie ds. Kultury i Ochrony Dziedzictwa Kulturowego Konferencji Episkopatu Polski, wersja z roku 2017, uaktualniona w roku 2018 i 2019, Uniwersytet Mikołaja Kopernika w Toruniu [Dampness - a problem of the guardian of the Church. Unpublished material, submitted to the Council for Culture and Protection of Cultural Heritage of the Polish Episcopal Conference, version from 2017, updated in 2018 and 2019, Nicolaus Copernicus University in Toruń], 1-42 (in Polish).
 
16.
Rouba, BJ 2023. Analiza klimatu w obiektach zabytkowych-kryteria oceny na przykładzie kościoła w Skępnem [Climate analysis in historic buildings - evaluation criteria on the example of the church in Skępne]. Ochrona Zabytków, 1, 193–228 (in Polish).
 
17.
Trochonowicz, M 2010. Wilgoć w obiektach budowlanych. Problematyka badań wilgotnościowych [Moisture in buildings. Problems of moisture testing]. Budownictwo i Architektura, 7, 131-144(in Polish).
 
18.
Czarnecki, L and Ściślewski, Z 1998. Wymagania dotyczące trwałości naprawianych konstrukcji żelbetowych [Durability requirements for repaired reinforced concrete structures]. Przegląd Budowlany, 11, 4-8 (in Polish).
 
19.
Arendarski, J 1978. Trwałość i niezawodność budynków mieszkalnych [Durability and reliability of residential buildings]. Warszawa: Wydawnictwo Arkady (in Polish).
 
20.
Praca zbiorowa pod redakcją Kamiński, M, Jasiczka, J, Buczkowski, W, Błaszczyński, T 2007. Trwałość i skuteczność napraw obiektów budowlanych [Durability and effectiveness of building repairs]. Wrocław: Dolnośląskie Wydawnictwo Edukacyjne (in Polish).
 
21.
Karyś, J 2014. Ochrona przed wilgocią i korozja biologiczną w budownictwie [Protection against moisture and biological corrosion in construction]. Warszawa: Wydawnictwo Dom Wydawniczy Medium (in Polish).
 
22.
Majewski, T and Niedostatkiewicz, M 2021. Uszkodzenia pożarowe dachu budynku kościoła pw. Świętych Apostołów Piotra i Pawła [Fire damage to the roof of the church of Saints Peter and Paul]. Przegląd Budowlany, 9, 603, 2-6 (in Polish).
 
23.
Kawecki, J 1991. Ocena szkodliwości drgań parasejsmicznych przekazywanych na kościoły zabytkowe [Assessment of the harmfulness of paraseismic vibrations transmitted to historic churches]. Inżynieria i Budownictwo, 6, 236-241 (in Polish).
 
24.
Kawecki, J and Stypuła, K 2009, 2009. Diagnozy a posteriori wpływów drgań drogowych na budynki [A posteriori diagnoses of the impact of road vibrations on buildings]. XXIV Konferencja Naukowo-Techniczna Awarie Budowlane-2009, 539-546, Szczecin-Międzyzdroje (in Polish).
 
25.
Niedostatkiewicz, M 2009. Usterki i uszkodzenia budynku mieszkalnego jako następstwo błędów projektowych nowo realizowanego sąsiedniego obiektu budowlanego [Defects and damages to a residential building as a consequence of design errors in a newly constructed adjacent Building]. XXIV Konferencja Naukowo-Techniczna Awarie Budowlane-2009, 671-678, Szczecin-Międzyzdroje (in Polish).
 
26.
Niedostatkiewicz, M and Majewski, T 2015. Uszkodzenia ścian konstrukcyjnych wielorodzinnego budynku mieszkalnego spowodowane błędami projektowymi i wykonawczymi [Damage to the structural walls of a multi-family residential building caused by design and construction errors]. XXVII Konferencja Naukowo-Techniczna Awarie Budowlane-2015, 649-656, Szczecin-Międzyzdroje (in Polish).
 
27.
Deneka, A, Rudziński, L and Grochal, W 1996. Adaptacja i modernizacja zabytkowego Spichrza Feuersteina na cele usługowo-handlowe [Adaptation and modernization of the historic Feuerstein Granary for commercial and service purposes]. VII Konferencja Naukowo-Techniczna Problemy Remontowe w Budownictwie Ogólnym, 315-324, Wrocław–Szklarska Poręba (in Polish).
 
28.
Frasunkiewicz-Puchalska, J and Tasarek, J 1996. Nadbudowa i modernizacja zabytkowego budynku bankowo-hotelowego [Extension and modernization of a historic bank and hotel Building]. VII Konferencja Naukowo-Techniczna Problemy Remontowe w Budownictwie Ogólnym, 325-332, Wrocław-Szklarska Poręba (in Polish).
 
eISSN:2450-8594
ISSN:2080-5187
Journals System - logo
Scroll to top